PermitsHubPermitsHub

Zoning & Bylaws

Can You Build a Fivеplex or Sixplex As-of-Right in Toronto?

Fourplexes are allowed across all of Toronto. Fiveplexes and sixplexes are not. They're permitted only in specific wards, and even there most projects that fail to stay as-of-right fail on building depth, height or lot frontage. Here's how to tell, before you buy or design, whether your lot can carry six units without a Committee of Adjustment hearing.

By PermitsHub Team9 min read

Key Takeaways

  • Toronto allows fourplexes citywide, but five and six unit multiplexes are permitted as-of-right only in a defined group of wards, so the first check is always the ward and the current bylaw text for that specific address.
  • Even inside an eligible ward, a sixplex only stays as-of-right if it fits the same building depth, height, setback and landscaping limits that govern a house on that lot, and those limits usually break first.
  • Past four units the Ontario Building Code asks more of the building, including heavier fire separations, protected exits and sometimes a fire alarm or sprinkler system, and those requirements take up floor area and push designs toward variances.
  • Servicing is the most underestimated step on a sixplex, because a larger water service, sewer capacity confirmation and waste storage can each reshape the site plan.

Six Units, Some Wards

Yes, but only in certain wards. Toronto permits up to four units on almost any residential lot citywide. Council later extended as-of-right permission for five and six units to a defined group of wards, concentrated in the older, inner parts of the city. Everywhere else, a fifth or sixth unit still needs a minor variance or a rezoning. Being in an eligible ward is also only the starting point. A sixplex has to fit the same building depth, height, setback and landscaping limits as any other building on that lot, and it has to meet tougher Ontario Building Code requirements than a fourplex. On most sixplex proposals, depth, height or a narrow frontage is what sends the project to the Committee of Adjustment.

Where the line sits: four units citywide, six units by ward

The fourplex permission is close to universal. If your lot is in a residential zone in Toronto's zoning bylaw, four units are allowed in principle, whether the lot is in Leaside or Malvern. The sixplex permission works differently. Council did not apply it citywide. It applies ward by ward, and the eligible wards are mostly pre-war neighbourhoods with older housing stock, transit nearby and lots originally laid out for semis, row houses and narrow detached homes.

Ward boundaries don't follow neighbourhood names, and they don't follow what a listing agent says about a street. We've seen buyers assume a sixplex was allowed because the house was 'basically in the east end,' and then find the lot sat one block outside the eligible ward. Check the address against the current ward map and the in-force bylaw text, not a news story. Bylaws get amended, appealed and phased in, and the version people repeat online may not be the one a plan examiner will apply to your file.

Outside the eligible wards, a fifth unit is a variance from the permitted number of dwelling units. Unit count is a more sensitive request at the Committee of Adjustment than an extra half metre of depth. It can be granted, but expect neighbour letters and a closer read from City Planning.

What as-of-right actually covers on a five or six unit building

As-of-right means the use is permitted. It doesn't mean any building that holds six units is permitted. The sixplex permission lets you have that many dwelling units in one building on the lot. It does not give you a bigger envelope than the zone already allows. The building still has to meet the performance standards for that zone: height, depth, side and rear setbacks, landscaping, and the rules about platforms, decks and projections.

This is where people get caught. Six units of a reasonable size need a lot of floor area, and the floor area has to fit inside a box set by depth, height and setbacks. On a deep, wide lot in Beaches-East York that can work. On a narrow lot with a tight side yard on one side, the box often can't hold six code-compliant units with their own exits, mechanical space and bike parking. So the designer either cuts units or starts asking for variances.

The sixplex permission tells you how many units you may have. The lot tells you how many you can actually fit, and on most Toronto lots those are two different numbers.

The zoning standards that push sixplexes to the Committee of Adjustment

Have a project in mind? Get an honest, no-pressure permit review from PermitsHub.

Across the multiplex files we've reviewed, the same few standards fail again and again. None of them is unique to sixplexes, but extra units put more pressure on each one.

Building depth

Depth is the most common trigger. A sixplex on a typical Toronto lot wants to stack two units per floor across three floors, or two per floor plus a lower level. Either way it runs long. The maximum building depth in your zone is fixed, and every metre beyond it is a variance. Rear additions on existing houses being converted hit this first, because the original house already uses much of the allowable depth.

Height and storeys

Six units on a modest footprint means going up. The height limit in many residential zones was written for houses, and a flat-roofed three-storey multiplex with a rooftop access stair or mechanical equipment can go over it. Toronto measures height in specific ways, including from established grade and with rules for what may project above the limit. A design that looks compliant on a sketch sometimes fails once grade is surveyed properly, especially on sloped lots.

Lot frontage and side yards

Narrow frontage hurts in two ways. First, side yard setbacks take a bigger share of a narrow lot, so the usable building width shrinks. Second, units at the back and on upper floors need a way out and a way in. If the only route to rear units is a side yard path, that path has to be wide enough and clear enough for daily use and for firefighters. On semi-detached lots and narrow detached lots, the remaining side yard often can't do that, and the design ends up needing a reduced setback or an unusual entrance layout.

Landscaping and projections

More units means more doors, more stairs, more bike racks and more bins, and they all end up in the front and rear yards. Soft landscaping minimums get eaten up fast. Exterior stairs, landings and balconies have their own projection limits. These variances are smaller but frequent, and each one is another item for the Committee and the neighbours to look at.

Why the building code gets harder past four units

This is the part of the brief that zoning maps don't show. A fourplex can often be designed much like a large house split into suites. A five or six unit building starts to look like a small apartment building to the Ontario Building Code. The jump isn't one rule. Several requirements tighten at once as unit count, occupant load and building height increase.

  • Fire separations: every unit has to be separated from every other unit and from shared spaces with rated assemblies, and with six units more of the interior becomes shared space that needs protection.
  • Exits: a shared stair serving upper units generally becomes an exit and has to be fire separated, sized and arranged to code, and whether a single exit is acceptable depends on storeys, travel distance and unit layout.
  • Fire alarm and detection: depending on the configuration, the building may need an interconnected fire alarm system rather than individual smoke alarms in each suite.
  • Sprinklers: some designers choose sprinklers to gain flexibility on separations or exits, which then makes the water service a design issue.
  • Sound transmission and access: more party walls and floors mean more assemblies that have to meet sound ratings, and accessibility requirements may apply depending on the building and the code edition in force.

Each of these takes space. A protected exit stair is an enclosed shaft running the full height of the building. Two of them can wipe out a unit. That's why fire and exiting decisions have to be made alongside the zoning analysis, not after it. If the code forces a second stair and the depth limit is already maxed out, you're heading to the Committee of Adjustment whether you planned to or not. Our basement suite fire separation articles cover the basics. A sixplex applies the same logic to every floor.

Plan examiners send sixplex drawings back on code more often than on zoning. Typical comments cover unclear fire separation continuity at floor and roof junctions, exit stairs that don't discharge directly outdoors, and spatial separation problems on side walls that sit close to the lot line, which limit how much window area you can have.

Servicing, waste and the items nobody plans for

Older houses in central Toronto often have a small water service, sometimes original or partly replaced. Six kitchens and six bathrooms, plus a sprinkler system if you have one, may need a larger service. That can mean a new connection from the main, which involves Toronto Water, a road cut and its own approvals and timing. Sanitary and storm connections get similar scrutiny. On some streets the City will want confirmation that the local sewer can take the added flow before it's comfortable with the permit.

Waste is the other surprise. Six households produce enough garbage, recycling and organics that curbside carts for each unit don't work well, and where the bins go affects landscaping, side yard clearance and the front elevation. Bicycle parking is in the same category. Toronto removed most minimum car parking requirements, but bike parking for multiplexes still has to be shown and has to fit.

Development charges and related fees also change with unit count. Some exemptions for additional units in a house don't extend to every unit in a five or six unit building. Confirm with the City what applies to your configuration before you finalize the pro forma, because it's one of the larger cost drivers on these projects. Under provincial rules, small residential projects of this size are generally exempt from site plan control, which removes one layer of review, but the building permit review itself is more involved than for a fourplex.

A five-minute test before you buy a lot or commission drawings

Have a project in mind? Get an honest, no-pressure permit review from PermitsHub.

Run these questions in order. If the answer to an early one is no, the later ones don't matter yet.

  • Is the address inside a ward where five or six units are permitted under the current, in-force bylaw?
  • Is the lot in a residential zone where the multiplex permissions apply, and is it free of overlays like ravine protection or heritage designation that add their own reviews?
  • Is the frontage wide enough to keep a usable side path to rear units after required setbacks?
  • Can six units, two exits if needed, mechanical space, bins and bikes fit inside the permitted depth and height, measured from real survey grades?
  • Does the existing water service and sewer connection have a realistic path to the capacity six units need?

If you get to the end with every answer yes, you probably have an as-of-right sixplex. If one or two answers are 'almost,' you're likely looking at a five-unit building as-of-right or a six-unit building with a small number of variances. Sometimes that's the better route, since the Committee generally sees minor depth or setback relief as more ordinary than a request to add units.

We've done this feasibility work on semis and narrow detached lots in Davenport, Toronto-Danforth and Parkdale, where the housing stock makes the five versus six decision very lot-specific. PermitsHub can run the zoning check against your exact address, test a unit layout against depth, height and exiting, and tell you before you spend on full drawings whether you're facing a clean permit or a Committee of Adjustment hearing.

Do I Need a Permit?

1
›
2
›
3
›
4

What are you planning to build or renovate?

Ready to move forward? PermitsHub handles permit drawings, submission, and revisions - flat-rate, GTA-wide.

Related Reading

More in this category

Zoning & Bylaws

FAQ

Related questions

Get started

Tell us about your project.

Free, no-pressure quote within one business day.

● Flat-rate quotes - no surprise fees

● Revisions included until approval

● Most enquiries responded to same day

Free Home Permit QuoteNo commitment · 30 sec
1
2
3

What are you building?

SCROLL TO SEE ALL 20 PERMIT TYPES

Prefer to call? 647-961-4070